By default, the buttons are not programmed. The buttons can be labeled to

indicate their function with a slip-in label. To operate the buttons, you must be

logged on with a level one password or greater.

Figure 45: Programmable keys

Key 1

Key 1 label
Key 2

Key 2 label

00:00:00 01/01/07

,

Note:

You cannot program a key while it is active. When the “Key is active”

message is displayed, wait until the key deactivates before continuing.

Table 19: Programmable key functions
Function

Option

Behavior when user key is pressed

None

User key does not respond.

Activate

Activates the outputs that belong to the correlation groups

associated with the user key.

Disable

Members

Disables all of the devices, NACs, and zones that belong to

the correlation groups associated with the user key with an

option of “Members.”

Disable

Group

Disables the correlation groups associated with the user

key with an option of “Group.” The devices, NACs, and

zones that belong to the correlation group remain enabled.

Disabled correlation groups do not activate even if the

required number of inputs activate. This is typically used to

prevent relay and sounder bases from sounding.

Disable

Members + Group

Disables all of the devices, NACs, and zones that belong to

the correlation groups associated with the user key with an

option of “Members + Group.” It also disables the

correlation group.