Edwards Signaling eFSA250 User Manual

Page 114

Advertising
background image

Chapter 2: Front panel programming

102

E-FSA64 and E-FSA250 Technical Reference Manual

Option

Description

Genesis non-silence: For Genesis and Enhanced Integrity horns and

strobes. Genesis and Enhanced Integrity appliances maintain

synchronization per UL 1971. For Genesis devices only, connected horns

cannot be silenced and strobes on the same two-wire circuit flash until the

panel is reset.
Genesis audible silence: For Genesis and Enhanced Integrity horns and

strobes. Genesis and Enhanced Integrity appliances maintain

synchronization per UL 1971. For Genesis devices only, it allows

connected horns to be silenced while strobes on the same two-wire circuit

continue to flash until panel reset.
Continuous silenceable: For strobes and notification appliances that self-

generate a temporal pattern
Continuous non-silenceable: For strobes and notification appliances that

self-generate a temporal pattern
Supervised: Lets you connect supervisory devices, such as a relay device

or switch
City tie: Outputs an unsynchronized, 24-volt continuous (steady) signal

that cannot be silenced or disabled. Select this NAC type when the NAC is

connected to a city tie module.

To program an input or output device:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Device.
4. If the panel has multiple loops, choose the loop to

be configured.

5. Enter the device address to be configured.

Note:

The device label occupies two lines just

below the device label.

6. Program each device in the system using Table 26

on page 95.

Note:

If you chose a dual address device, both

addresses for the device are displayed on the

screen (e.g. 001/002). The first address listed is

the device address you are programming. When

you pick the second address to program, both

addresses are still displayed but the order is

reversed (e.g. 002/001).

Loop Configuration

Loop class

Zone

Correlation Groups

Device

Device

Loop 01<>

Device

Number 001

Device label line 1

Device label line 2

Device 001

Zone 01<>

Label <>

Event notification

Correlation Groups

Day Sens Normal<>

Night Sens Normal<>

Day PreAlarm% 50<>

Night PreAlarm% 50<>

Base Type Sounder<>

Follow Alarm<>

Type Smoke<>