Chapter 2: Front panel programming

92

E-FSA64 and E-FSA250 Technical Reference Manual

Yes to add a panel event
No to remove a panel event

7. Choose Save.

Add/Remove Device

Add/Rem Panel Event

Add/Rem Panel Event

Reset Activate No<>

Reset Restore No<>

Signal Silence No<>

Programming in-suite signal silence

In-suite signal silence is programmed using two separate menus:
• Configure the elapse timer for in-suite signal silence by displaying the

Program > Advanced Program > Panel Operation menu.

• The function is enabled for individual correlation groups through the

Program > Advanced Program > Loop Configuration > Correlation Groups

menu.

This section provides instructions for setting both in-suite signal silence options.

Note:

When setting up correlation groups for in-suite signal silence, the group’s

activation count must be set to 1. See “Setting a correlation group’s activation

count” on page 88.

To enable in-suite signal silence for a correlation group:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3 Choose Loop Configuration.
4. Choose Correlation Groups and enter the number

of the correlation group. (Values range from 001 to

199.)

5. Choose Suite Sig Sil.
6. Select:

Yes to enable in-suite signal silence.
No to disable it.

7. Choose Save.

Advanced Program

Loop Configuration

Loop Configuration

Loop Class

Zone

Correlation Groups

Correlation Groups

Number 001<>

Correlation Group 001

Add/Remove Zone

Add/Remove NAC

Add/Remove Device

Suite Sig Sil YES<>

Correlation Group 001

Copy 001

Remove All

Save

Advertising