Chapter 3: System operation

154

E-FSA64 and E-FSA250 Technical Reference Manual

Event ID numbers and descriptions

Table 43: Event ID numbers and descriptions
ID

Event description

000 Loop 1 initialization:

Loop 1 is starting

up

001 Loop 1 fault: A short or open was

detected on loop 1 affecting the

communications between the panel and

the devices on the loop

002 Not used

003 Loop 1 card fault: The loop 1 card is not

present or it is not working properly

004 Loop 1 uncfgrd alarm: A device on loop

1 that is not programmed went into

alarm

005 Loop 1 uncfgrd trouble: A device on

loop 1 that is not programmed went into

trouble

006 Not used

007 Loop 1 over limits: There are too many

devices on loop 1

008 Loop 1 device 000: A device on loop 1

has an address set to zero

009 Not used

ID

Event description

010 Loop 2 initialization:

Loop 2 is starting

up

011 Loop 2 fault: A short or open was

detected on loop 2 affecting the

communications between the panel and

the devices on the loop

012 Not used

013 Loop 2 card fault: The loop 2 card is not

present or it is not working properly

014 Loop 2 uncfgrd alarm: A device on loop

2 that is not programmed went into

alarm

015 Loop 2 uncfgrd trouble: A device on

loop 2 that is not programmed went into

trouble

016 Not used

017 Loop 2 over limits: There are too many

devices on loop 2

018 Loop 2 device 000: A device on loop 2

has an address set to zero

019 Not used