Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

113

3. Enter the NAC (number) you want to program, and

then press Enter.

Note:

NAC 3 and 4 are not available if either NAC

1 or 2 or both are set to Class A.

4. Program each NAC in the system using Table 30

on page 110.

5. When you finish programming each option,

choose Save.

6. Press the Menu button to exit menu mode, or

continue programming.

Annunciator

Panel NAC

NAC 1<>

Panel NAC 1

Class Class A<>

Type Cont. Non Sil<>

Label >

Panel NAC 1

Correlation Groups

Event Notification

Save

Setting annunciator classes

Program the annunciators’s wiring class (Class A or Class B). You must install

the optional SA-CLA module if you have class annunciator wiring on the 64 point

panel.
Default: Class B

To set the annunciator class:

1. Display the panel configuration options menu. See

“Panel programming” on page 109.

2. Choose Ann. Class.
3. Select either Class A or Class B.
4. Program other panel configuration options or

choose Save if you’re finished.

5. Press the Menu button to exit menu mode, or

continue programming.

Panel Configuration

Panel NAC

Ann. Class A<>

Annunciator

Panel Configuration

Ann. Class A<>

Annunciator

Save

Annunciator programming

Each annunciator on the annunciator loop must be programmed for type, number

of expanders, label, and event notification. Up to eight annunciators can be

connected on the loop and each must be programmed separately. You must also

set the address on each annunciator by using the DIP switch on the back of the

annunciator.