Chapter 2: Front panel programming

132

E-FSA64 and E-FSA250 Technical Reference Manual

6. Set the event notification. See the default settings

in the table above.
Printer: Yes or No. Specifies if event information is

printed.
Dialer:
• Acct 1 & 2: Event information is sent to both

dialer accounts

• Acct 1: Event information is sent to dialer

account one

• Acct 2: Event information is sent to dialer

account two

• None: Event information is not sent to the

dialer

NET (1-8): Yes or No. Specifies if event

information is sent to the connected network
CID: Contact ID event code (000 to 999)

7. When finished, choose Save.
8. Repeat steps 6 to 9 for each loop event.
9. Press the Menu button to exit menu mode, or

continue programming.

Loop 1 Initializing

Event Notification

Active

Printer Yes<>

Dialer Account 1&2

CID 110

NET(1-8) Yes<>

_Save

Unconfigured alarm event programming

You can assign the unconfigured alarm event a correlation group and use it to

turn on an output device. When assigned to a correlation group, every

unconfigured alarm event turns on every output device in the correlation group.

You can also program the event notification can for the unconfigured alarm. Auto

programming will not assign an unconfigured alarm to a correlation group.

To program the unconfigured alarm event:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Unconfigured Alarm.
4. Choose Loop 1 Uncfgrd Alarm or Loop 2 Uncfgrd

Alarm. (The second option is displayed only if you

have more than one loop).

Advanced Program

Loop Events

Unconfigured Alarms

Common Trouble

Unconfigured Alarms

Loop 1 Uncfgrd Alarm

Loop 2 Uncfgrd Alarm

Loop 1 Uncfgrd Alarm