Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

41

Table 8: Contact ID event codes
Event

CID

AC power (disable)

500

AC power (trouble)

301

Alarm active

110

Annunciator trouble

334

Aux. power 1 (disable)

500

Aux. power 1 (trouble)

312

Aux. power 2 (disable)

500

Aux. power 2 (trouble)

312

Battery charger (disable)

500

Battery charger (trouble)

309

Battery low (disable)

500

Battery low (trouble)

302

Battery missing (disable)

500

Battery missing (trouble)

311

Clear history

621

Common alarm

110

Common disable

500

Common monitor

140

Common supervisory

200

Common trouble

373

Common trouble for network dialer 373
Common trouble for telco dialer

373

Date

625

Device trouble

373

Device disable

570

Device pre alarm

118

Device alarm verify

118

Device maintenance alert

393

Device test

614

Dialer disable/remote disconnect

551

Event

CID

Dialer line 1 fault (disable)

500

Dialer line 1 fault (trouble)

351

Dialer line 2 fault (disable)

500

Dialer line 2 fault (trouble)

352

Dialer deliver fail

354

Dialer normal test

602

Dialer abnormal test

608

Dialer configuration

354

Drill

601

Duct active

116

Ground fault (disable)

500

Ground fault (trouble)

310

Heat active

114

Internal fault

307

IP Gateway Trouble

354

Loop 1 initialization

000

Loop 1 fault (disable)

500

Loop 1 fault (trouble)

331

Loop 1 card fault (disable)

500

Loop 1 card fault (trouble)

333

Loop 1 Uncfgrd alarm (disable)

500

Loop 1 Uncfgrd alarm (active)

110

Loop 1 Uncfgrd trbl (disable)

500

Loop 1 Uncfgrd trbl (trouble)

331

Loop 1 over limits

331

Loop 1 address zero

331

Loop 2 initialization

000

Loop 2 fault (disable)

500

Loop 2 fault (trouble)

331

Loop 2 card fault (disable)

500

Loop 2 card fault (trouble)

333