Chapter 2: Front panel programming

88

E-FSA64 and E-FSA250 Technical Reference Manual

To add the Common Trouble Event to a correlation group:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Common Trouble then choose Trouble.
4. Choose Correlation Groups and enter the number

of the correlation group to be configured.

5. Press Enter to toggle between possible values:

• “Included” adds the item to the group

• “Excluded” removes the item from the group

6. Repeat steps 7 to 9 to add or remove the event

from any remaining correlation groups to be

configured.

7. Choose Save.
8. Press the Menu button to exit menu mode or

continue programming.

Trouble

Correlation Groups

Event Notification


Correlation Groups

Group 001

Status Included

Enter Exit

Setting a correlation group’s activation count

A correlation group’s activation count is the number of member activations that

are required to activate the correlation group. The activation count is used to set

up cross zoning. The following rules apply: disservice
• The count cannot exceed the number of input members in the correlation

group

• The default value is 1

• Input members can be zones, NACs, devices, unconfigured alarm events, or

the common trouble event

• The activation count must be 1 for correlation groups with in-suite signal

silence enabled

• The activation count must not exceed 2 for cross zoning applications and the

zones should not have alarm verification per ANSI/NFPA 72-2002 6.8.5.4.3.