Chapter 5: Diagnostics, maintenance, and testing

E-FSA64 and E-FSA250 Technical Reference Manual

195

Recalibrate device

The Recalibrate command resets a detector’s environmental compensation and

dirtiness level. You can use this command after cleaning to see immediately

whether the device was cleaned properly. Allowing the panel to recognize that

the device has been cleaned and recalibrate it automatically takes considerably

more time. A device trouble will return, indicating that more cleaning is required.

If the device is cleaned, the corresponding device trouble will clear.

To recalibrate a device:

1. Press the menu button and choose Diagnostics.
2. Enter a level two password.
3. Choose Recalibrate Device.
4. Choose the loop the device is on.

Note:

If the panel only has one loop, the loop

selection screen does not display. Go to the next

step.

5. Choose the number of the device that you want to

recalibrate.

6. Press Enter.

Test

Control

Program

Diagnostics

Enter Password

0000

Diagnostics

Fast Ground Check

Recalibrate Device

Flash Device LED

Recalibrate Device

Loop 01<>

Recalibrate Device

Device 001

Device 001

Flash device LED

Flash Device LED is used to help in troubleshooting to locate a device on a loop

by flashing the device’s LED (detectors flash red LED, modules flash green

LED). By selecting a specific device and flashing its LED, you can quickly locate

the device on the loop. One way to use this for, example, is if you have two

devices with the same address (duplicate address), you can flash the LED for

that device address, which causes the LED to flash on the two devices with the

same address, making it easy for you to find the two devices.

To start and stop flashing a device LED:

1. Press the menu button and choose Diagnostics.