Table 37: Default loop event settings
Loop event

Printer

Dialer

NET (1-8) CID

Loop 1 initialization

Yes

None

No

n/a

Loop 1 fault (disable)

Yes

None

No

n/a

Loop 1 fault (trouble)

Yes

Acct 1

No

331

No

Loop 1 card fault (disable) (e.g. line fault)

Yes

None

No

n/a

Loop 1 card fault (trouble) (e.g. line fault)

Yes

Acct 1

No

333

Loop 1 Uncfgrd alarm (disable)

Yes

None

No

n/a

Loop 1 Uncfgrd alarm (trouble)

Yes

Acct 1

No

110

Loop 1 Uncfgrd trbl (disable)

Yes

None

No

n/a

Loop 1 Uncfgrd trbl (trouble)

No

None

No

n/a

Loop 1 over limits

Yes

None

No

n/a

Loop 1 address zero

Yes

None

No

n/a

Loop 2 initialization

Yes

None

No

000

Loop 2 fault (disable)

Yes

None

No

500

Loop 2 fault (trouble)

Yes

Acct 1

Yes

331

Loop 2 card fault (disable) (e.g. line fault)

Yes

None

No

500

Loop 2 card fault (trouble) (e.g. line fault)

Yes

Acct 1

No

333

Loop 2 Uncfgrd alarm (disable)

Yes

None

No

500

Loop 2 Uncfgrd alarm (trouble)

Yes

Acct 1

No

110

Loop 2 Uncfgrd trbl (disable)

Yes

None

No

500

Loop 2 Uncfgrd trbl (trouble)

No

None

No

331

Loop 2 over limits

Yes

None

No

331

Loop 2 address zero

Yes

None

No

331

To program loop events:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Loop Events.
4. Select the loop event.
5. Choose Event Notification.

Advanced Program

Panel Operation

Panel Events

Loop Events

Loop Events

Loop 1 Initializing