Edwards Signaling eFSA250 User Manual

Page 145

Advertising
background image

Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

133

5. Choose Correlation Groups and enter the number

of the correlation group.

6. Press Enter to toggle between possible values:

To add the event to the group, choose Included.
— or —
To remove it from the group, choose Excluded.

7. Repeat steps 7 to 9 to add or remove the event

from any remaining correlation groups to be

configured.

8. Choose Save.
9. Choose Event Notification.
10. Choose Active.
11. Configure active event notification. (Not all the

options shown here are displayed on all systems.)
Printer: This controls whether event information is

sent to the printer. Press Enter to toggle between

Yes and No.
Coder: Four-digit coded output that is played in

response to alarm conditions (00-00-00-00 to 99-

99-99-99).
Dialer options are listed below.
• Acct 1 & 2: Event information is sent to both

dialer accounts

• Acct 1: Event information is sent to dialer

account one

• Acct 2: Event information is sent to dialer

account two

• None: Event information is not sent to the

dialer.

CID: Contact ID event code (000 to 999).
NET (1-8): Yes or No. This controls whether event

information is sent to the connected network.

12. When you have finished, choose Save.
13. Press the Menu button to exit menu mode, or

continue programming.

Correlation Groups

Event Notification

Correlation Groups

Group 001

Status Included

Enter Exit

Unconfigured Alarm

Correlation Groups

Event Notification

Event Notification

Active

Active

Printer Yes<>

Code 10-10-10-10

Dialer Account 1&2

CID 110

NET(1-8) Yes

_Save