Chapter 2: Front panel programming

76

E-FSA64 and E-FSA250 Technical Reference Manual

Device option Description

Photoelectric smoke detectors

Smoke: For smoke detectors and contact devices. All activations are

immediately considered as alarms. Circuit cannot be restored until devices

are restored to normal and the panel is reset.
Smoke verified: For smoke detectors and contact devices. Two-wire smoke

detector activations are verified (delayed and confirmed) before activating an

alarm. Four-wire smoke detectors and contact devices are not verified and

immediately considered as alarms. Circuit cannot be restored until devices

are restored to normal and the panel is reset.
Supervisory latching: For detectors that trigger an active (supervisory) event.

Detectors with this device type remain active until the condition that

activated them is restored and the control panel is reset.
Supervisory nonlatching: For detectors that trigger an active (supervisory)

event. Detectors with this device type remain active until the condition that

activated them is restored. Resetting the control panel is not required.

Duct detectors

Duct alarm: For duct smoke detectors. All activations are immediately

considered as alarms. Circuit cannot be restored until devices are restored

to normal and the panel is reset.
Duct supervisory latching: Detectors with this device type when activated

immediately places the panel in the supervisory state, turns on supervisory

LEDs, and activates the supervisory relays. The detectors remain active until

the smoke condition clears and the panel is reset.
Duct supervisory nonlatching: Detectors with this device type when activated

immediately places the panel in the supervisory state, turns on supervisory

LEDs, and activates the supervisory relays. The detectors remain active until

the smoke condition clears. Resetting the panel is not required.

Heat detectors

Heat alarm: For heat detectors and contact devices. All activations are

immediately considered as alarms. Circuit cannot be restored until devices

are restored to normal and the panel is reset.
Heat alarm RoR: For heat detectors and contact devices with rate-of-rise. All

activations are immediately considered as alarms. Circuit cannot be restored

until devices are restored to normal and the panel is reset.