Appendix D: Applications

E-FSA64 and E-FSA250 Technical Reference Manual

261

Correlated zone and system alarm signaling

applications

Correlated signaling applications are those in which sounder bases are triggered

by associated correlation groups. This includes zone alarm and system alarm

signaling applications. Detectors are added to the input side, and polarity

reversal modules s are added to the output side of one or more correlation

groups.

Zone alarm signaling applications

What is zone alarm signaling?

In zone alarm signaling applications, detectors and sounder bases are grouped

by zone. All sounder bases within a zone automatically sound alarm signals

when any detector in the zone initiates an alarm event.
Since alarm signals are limited to the same notification zone, signal

synchronization is not required. The sounder bases, once activated, continue to

sound an alarm signal until:
• Smoke is cleared from the active detectors and the control panel is reset.
• Signal Silence is pressed.
• The control panel’s Auto Signal Silence timer expires, if programmed. This

can be from 5 to 30 minutes.

• The in-suite signal silence timer expires, if programmed. (See “What is in-

suite signal silence?” on page 34 and on page 92.

Typical wiring for zone alarm signaling

The 24 VDC riser that supplies power to the sounder bases is supervised using

an IDC1B Single Input module and a 24 VDC Control Relay.