Chapter 2: Front panel programming

94

E-FSA64 and E-FSA250 Technical Reference Manual

To add sounder base detectors to a fast group:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Correlation Groups and enter the

correlation group number to be programmed.

Enter a value from:
• For panels with one loop only, the fast

correlation groups are Groups 001 to 025

• For panels with two loops, the fast correlation

groups are
Loop 1: groups 001 to 025
Loop 2: groups 001 to 025 or 101 to 125 (user

configurable).

See “Programming fast groups for sounder bases”

on page 93.

4. Choose Add/Remove Device.
5. Enter the loop number (if the panel has multiple

loops).

6. Enter the device number.
7. Add the detector as an input and the sounder base

as an output. Choose:
Sensor to add the detector
— or —
Base to add the sounder base

8. On the Status line, press Enter to select Included.

This adds the device to the group.

9. Repeat steps 4 to 8 to add or remove other

devices, zones, or NACs.

10. Repeat steps 3 to 9 to program additional

correlation groups.

11. Press the Menu button to exit menu mode, or

continue programming.

Loop Configurationxxx

Loop Class

Zone

Correlation Groups

Correlation Groups

Number 001<>

Correlation Group 001

Add/Remove Zone

Add/Remove Device

Add/Rem Panel NAC

Add/Remove Device

Loop 02

Add/Remove Device

Device 001<>

Device 001

Add/Remove Sensor

Add/Remove Base

Add/Remove Sensor 001

Status Included