Chapter 2: Front panel programming

38

E-FSA64 and E-FSA250 Technical Reference Manual

• Event notification

Trouble > Printer: Yes

Trouble > Dialer: Acct 1

Trouble > NET (1-8): No

Trouble > CID: 321 (NAC1), 322 (NAC2),

326 (NAC3), 327 (NAC4)

Disable > Printer: Yes

Disable > Dialer: Acct 1

Disable > NET: Yes

Disable > CID: 521 (NAC1), 522 (NAC2), 526

(NAC3), 527 (NAC4)

Test > Printer: Yes

Test > Dialer: Acct 1

Test > CID: 600

Test > NET (1-8): No

• Annunciator class: Class B
• Annunciators (1-8)

Type: Off

Number expanders: None

Event notification

Trouble > Printer: Yes

Trouble > Dialer: Acct 1

Trouble > CID: 334

Trouble > NET (1-8): No

• Swinger shutdown: Off

• CMS device

Dialer

Type: Dual line

Acct 1 and 2

Account ID: FFFF

Primary receiver #: Blank

Secondary receiver #: Blank

Format: CID

Line 1 and 2

Dialing: Tone

Cut Duration/supervision: 120 sec.

Tone wait: 10 seconds

Call disconnect seconds: Off

Test frequency days: 1

Send restorals: Yes

Retry time: 5 seconds

Retry count: 5

Event notification: Device

Test time: 03:11

Rings to answer: 5

Ring type: Any

Callback: Disabled

Callback #: Blank

• Printer

Type: Unsupervised

Event notification

Trouble > Printer: Yes

Trouble > Coder: 00-00-00-00

Trouble > Dialer: Acct 1

Trouble > CID: 336

Trouble > NET (1-8): No

• Lock remote read: No
• AC voltage: 120

• Network (receiver)

Enabled: No

Account ID: FFFF

IP: 192.168.1.254

TCP/IP port: 9999

Send restorals: Yes

Event notification: Device

Hello time: 25

Timeout: 40

Receiver #: 2

Line #: 2

Advertising