Edwards Signaling eFSA250 User Manual

Page 99

Advertising
background image

Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

87

To add or remove members from a correlation group:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Correlation Groups and enter the

correlation group number to be programmed.

(Values range from 001 to 199.)

4. Choose:

• Add/Remove Zone to add or remove a zone

• Add/Rem Panel NAC to add or remove a NAC

• Add/Rem Device to add or remove a device

Note:

The Add/Rem device includes primary

sensor, secondary sensor, and base, if

applicable.

• Add/Rem Panel Event

• Suite Sig Sil

• Activation Count

• Delay

• Copy

• Remove All

• Save

5. Enter the loop number (if the panel has multiple

loops).

6. Enter the zone, NAC, or device number.
7. On the Status line, press Enter to select Included

or Excluded:
• “Included” adds the item to the group

• “Excluded” removes the item from the group

8. Repeat steps 4 to 7 to add or remove other

devices, zones, or NACs.

9. Repeat steps 3 to 9 to program additional

correlation groups.

10. Press the Menu button to exit menu mode, or

continue programming.

Loop Configuration

Loop Class

Zone

Correlation Groups

Correlation Groups

Number 001<>

Correlation Group 001

Add/Remove Zone

Add/Remove Device

Add/Rem Panel NAC

Add/Remove Device

Device 001<>

Status Excluded

<-Enter <-Cancel