Chapter 1: Installation and wiring

E-FSA64 and E-FSA250 Technical Reference Manual

27

RPM module wiring

The Reverse Polarity Module (RPM) is an interface between the control panel

and a reverse polarity receiver. It provides off-premises signal transmission for

systems that must comply with NFPA requirements. When used as a reverse

polarity remote station transmitter, it can be connected to either a single circuit

(alarm or alarm and trouble) or up to three circuits (alarm, supervisory, and

trouble). Below are application diagrams for using the RPM module. For detailed

information and wiring, refer to the RPM Installation Sheet (P/N 3100430).

Notes

• The RPM must be mounted in conduit, in an MFC-A enclosure, immediately

adjacent to the panel.

• All relays are unsupervised and must be connected to a power-limited source.

Figure 39: Terminal wiring location

Figure 40: Alarm transmitted only

TRBL C

NC

SUP

NC

ALM

24VOUT

Control panel

TB3

+

NO

From COM on RPM (black wire)
From +24 on RPM (red wire)

C

NO

+

From ALRM on RPM (brown wire)

Advertising