Chapter 1: Installation and wiring

E-FSA64 and E-FSA250 Technical Reference Manual

17

Circuit specifications

• Circuit voltage range: 21.9 to 28.3 V
• AUX 1 + AUX 2 can supply 1.5 A total. If more than 1.5 A is required, you

must use a power-limited and regulated 24 VDC auxiliary/booster power

supply that is UL/ULC and FM Listed (if the installation requires FM

regulation) for fire protective signaling systems.

• For a complete list of auxiliary/booster power supplies, refer to the VS1 and

VS2 Series Compatibility List (P/N 3101065). Also refer to the Technical

Reference Manual (P/N 387515) for a list of compatible power supplies, if

you need to power GSA-REL module.• Continuous circuit (AUX power 1): 24

VDC nominal at 500 mA. Use this circuit to supply 24 VDC continuous power.

• Resettable circuit (AUX power 2): 24 VDC nominal at 500 mA (1 A possible if

you reduce total available NAC power by 500 mA). Use this circuit to provide

24 VDC resettable power. You can configure AUX power 2 as a continuous

circuit if you do not need a resettable circuit.

• Special application circuits
• Ground fault impedance: 0 to 5 kΩ
• Supervised and power-limited

Figure 24: Auxiliary/smoke power wiring location