Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

109

Printer: Yes or No. This controls whether event information is

sent to the printer
Dialer:
• Acct 1 2: Event information is sent to both dialer accounts
• Acct 1: Event information is sent to dialer account one
• Acct 2: Event information is sent to dialer account two
• None: Event information is not sent to the dialer
NET: Yes or No. Controls whether event information is sent to

the connected network
CID: Contact ID event code (000 to 999)

To program a zone:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Loop Configuration.
4. Choose Zone and enter the zone number.
5. Program each zone in the system using Table 29

on page 108.

6. When you finish programming an option, choose

Save, and then continue.

7. Press the Menu button to exit menu mode, or

continue programming.

Loop Configuration

Loop Class

Zone

Correlation Groups

Zone

Number 01>

Zone 01

Zone 01

Type Alarm<>

Label >

Correlation Groups

Zone 01

Correlation Groups

Event Notification

Save

Panel programming

The panel options to be configured include:
• NAC circuits (“NACs”)

• Annunciator class

• Annunciator

• Dialer and network (“CMS device”)

• Printer

• IP address (“IP”)

• Subnet mask (“MSK”)

• Gateway (“GWY”)

Most options have a factory default setting that you can accept or change. See

“Factory default settings” on page 36.