Battery calculation worksheet – Edwards Signaling eFSA250 User Manual

Page 224

Advertising
background image

Appendix B: Worksheets

212

E-FSA64 and E-FSA250 Technical Reference Manual

Battery calculation worksheet

Use this worksheet to determine the minimum amp hour capacity required for the

panel’s standby battery. You can obtain operating current requirements for

notification appliances from their respective installation sheets.

Battery calculation worksheet

Standby

current (mA)

Alarm

current (mA)

Control panel

(use Worksheet A and place totals

here)

Auxiliary/smoke power

(use Worksheet B and place totals

here)

NAC 1

NAC 2

NAC 3

NAC 4

Total current

Operating time required

×

hr

×

min

÷ 60

+

=

mAh

×

1.2

mAh

÷

1,000

Battery size [1]

Ah

[1] Battery size may not exceed 26 Ah for UL/ULC systems. See Appendix A “Panel

specifications” on page 207 and “Battery wiring (TB8)” on page 7 for battery details.