Edwards Signaling eFSA250 User Manual

Page 109

Advertising
background image

Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

97

Option

Description

is set for alarm verification.

• If the detector is set for alarm verification, the base activates when the

detector goes into alarm verification. It does not restore, however, until the

alarm restores.

• The base does not respond when the detector goes into prealarm no

matter how the detector is configured. Also, the base only follows the

primary element of a dual element detector. Any activation from a

secondary element does not trigger the base.
Example: When a PCOS on a sounder base has a follow set to Head, the

base is only triggered when a smoke event is generated. The base does

not trigger when a CO event is generated.

Riser: The base is triggered individually by the panel (sounder bases only)
None: A correlation group triggers the base. The opton “None” can be applied

to both relay and sounder bases, and is used for relay bases configured as

latched output devices.

Note:

All base follow settings except Head and Riser can be activated by

correlation groups.
Alarm: The base activates its relay when the detector goes into alarm. The

base will not restore until the alarm event has been restored.
Alarm and verify (ALM+VFY): The base activates its relay when the detector

goes into alarm verify and continues when the detector goes into alarm. The

base will not restore until both events have been restored.
Alarm and prealarm (ALM+PALM): The base activates its relay when the

detector goes into prealarm and continues when the detector goes into an

alarm. The base will not restore until both events have been restored.

Type

Select the device type based on the type of device you are programming.

Note:

Available device types depend on the device and the marketplace

selected for the panel. Some device types are not available in some

marketplaces. For this reason, the LCD listing for the selected device may

differ from this table.
Duct detectors (SD)

Duct alarm: For duct smoke detectors. All activations are immediately

considered as alarms. Circuit cannot be restored until devices are restored

to normal and the panel is reset.
Duct supervisory latching: Detectors with this device type when activated

immediately places the panel in the supervisory state, turns on

supervisory LEDs, and activates the supervisory relays. The detectors

remain active until the smoke condition clears and the panel is reset.
Duct supervisory nonlatching: Detectors with this device type when

activated immediately places the panel in the supervisory state, turns on

supervisory LEDs, and activates the supervisory relays. The detectors

remain active until the smoke condition clears. Resetting the panel is not

required.

Advertising
This manual is related to the following products: