4 scope of delivery, 5 accessories, 4 installation – Xylem ECOCIRC XL & XLplus User Manual

Page 18: 1 pump handling, 2 facility requirements, 1 pump location

Advertising
background image

Feature

Description

Motor model Electronically commutated motor

with permanent magnet rotor

Series

ecocirc XL
ecocirc XLplus

Rated voltage 1 x 230 V ±10%
Frequency

50/60 Hz

Power con-

sumption

40÷1700 W

IP protection IP 44
Insulation

class

Class 155 (F)

Maximum

working pres-

sure

The maximum pressure is indicat-

ed on pump data plate
0.60 MPa (6 bar)
1.0 MPa (10 bar)

Permitted liq-

uid tempera-

ture

The maximum temperature is indi-

cated on pump data plate
from -10°C (14°F) to +110°C

(230°F) for heating pumps
from -10°C (14°F) to +85°C (185°F)

for domestic hot water pumps

Permitted

ambient tem-

perature

from 0°C (32°F) to 40°C (104°F)

Permitted

ambient hu-

midity

< 95%

Permitted

pumping me-

dia

Heating water according to VDI

2035, water/glycol mixtures

10

up to

50%.

Sound pres-

sure

≤ 43 dB (A)

EMC (electro-

magnetic

compatibility)

EN 55014-1:2006 + A1:2009 +

A2:2011, EN 55014-2:1997 +

A1:2001 + A2:2008, EN

61000-3-2:2006 + A1:2009 +

A2:2009, EN 61000-3-3:2008,

61800-3:2004+A1:2012.

Leakage cur-

rent

< 3.5 mA

I/O auxiliar

+15 VDC

power supply

(Not available

on 25-40,

25-60, 32-40,

32-60 mod-

els)

Imax < 40 mA

Fault signal

relay

Vmax < 250 VAC
Imax < 2 A

3.4 Scope of delivery

Inside the package you will find:

• Pump unit

• Insulating shells (single head only)

• Gasket (OR) to be used as replacement for the

OR mounted between motor and pump hous-

ing

• Plug connector (for 25-40, 25-60, 32-40, 32-60

models only)

• Seal for threaded connection (only for threaded

pump housing)

• Seal for flanged connection (only for flanged

pump housing)

• Eight M12 washers and eight M16 washers (for

models from DN32 to DN65)

• Eight M16 washers (for DN80 and DN100 PN6

model)

• Sixteen M16 washers (for DN80 and DN100

PN10 models)

3.5 Accessories

• Counter flanges

• Blind flanges

• Port to port adapters

• Pressure sensor (for details see section 5.2.9 of

this manual)

• Temperature probe (for details see section

5.2.9 of this manual)

• RS485 module (only for ecocirc XLplus)

• Wireless module (only for ecocirc XLplus)

4 Installation

Precautions

WARNING:

• Observe accident prevention regu-

lations in force.

• Use suitable equipment and protec-

tion.

• Always refer to the local and/or na-

tional regulations, legislation, and

codes in force regarding the selec-

tion of the installation site, plumb-

ing, and power connections.

4.1 Pump handling

WARNING:
Observe local regulations setting the

limits for manual lifting or handling.

Always lift the pump by the pump head or pump

housing. If the pump weight exceeds the manual

handling limits, use lifting equipment, positioning

lifting straps according to

Figure 11

.

4.2 Facility requirements

4.2.1 Pump location

DANGER:
Do not use this unit in environments

that may contain flammable/explosive

or chemically aggressive gases or pow-

ders.

10

Performance of the pump is referred to water at 25°C (77°F). Pumped media with different viscosity will have impact
on such performances.

en - Translation of the original instructions

18