9 analog input, 10 signal relay, 11 external sensors – Xylem ECOCIRC XL & XLplus User Manual

Page 24

Advertising
background image

5.2.8 PWM input (available only on 25-40,
25-60, 32-40, 32-60 models)

Only on the listed models, the PWM input is availa-

ble on terminals 11 and 12. See

Figure 18

.

The PWM signal shares the same terminals of the

start/stop input.
The two inputs are mutually exclusive.
For details, refer to advanced functions manual on

www.lowara.com

5.2.9 Analog Input

The pump integrates a 0-10 V analog input at ter-

minals 7 and 8. See

Figure 18

and

Figure 19

for

changing the set point.
When a voltage input is detected, the pump switch

to fix speed control mode automatically and start

to work according to the following diagram:

Vin[V]

Speed

[rpm]

Vset

10

1,5

1,2

min

Max

Setpoint

5.2.10 Signal relay

The pump is equipped with a relay, terminals 4 and

5. See

Figure 18

and

Figure 19

, for a potential-free

fault signal. If there is a fault the relay is activated

together with the red status light and the error

code on the user interface display,

Figure 13

.

Ratings

• Vmax < 250 VAC

• Imax < 2 A

5.2.11 External sensors

The pump can be equipped with a differential

pressure sensor and a temperature probe accord-

ing to the following table:

Sensor descrip-

tion

Type

Terminals

Differential

pressure sensor

4-20mA

1.0 bar (PN 10)
2.0 bar (PN 10)

9 - 10

External tem-

perature sensor

KTY83

13 - 14

Pressure sensor setup

1. Install the pressure sensor on the pipe

2. Connect the cable at terminals 9 and 10 (see

the 4.6.3 Connection assignment).

3. Power on the pump unit.

4. During startup the pump unit detects the sen-

sor and shows a setup menu.

5. Select the right sensor model and confirm the

selection using the parameter button (3). See

Figure 13

.

6. The pump will complete the startup sequence

and automatically start working with constant

pressure mode.

7. The setpoint can be changed using the setting

buttons (5). See

Figure 13

.

External temperature sensor setup (only for eco-

circ XLplus)
The setup of the sensor and control modes related

to it, is available only through communication bus.
For details refer to communication and advanced

functions manuals on www.lowara.com

NOTICE:
The sensor cables shall not exceed 20 m.

5.2.12 Communication bus (available only
on ecocirc XLplus)

The pump has two built-in RS-485 communication

channels. One is available as standard (terminals

15-16-17), while the second one is enabled only

with optional RS-485 or Wireless module (terminals

18-19-20). See

Figure 18

and

Figure 19

.

The pump can communicate with external BMS sys-

tems via Modbus or BACnet

12

protocol. For a com-

plete description of the protocols, refer to the com-

munication manual at www.lowara.com.

NOTICE:
When remote control is active, the set points and

control modes are managed only through commu-

nication channels and cannot be changed via the

user interface. The displayed quantity and unit of

measurement management remain active on user

interface.

5.2.13 Automatic twin pump operation
(available only on ecocirc XLplus)

Backup operation
Only the master pump runs. The second pump

starts in case of failure of the master pump.
Alternate operation
Only one pump runs at the time. The working time

is switched every 24 hours so that workload is bal-

anced between both pumps. The second pump is

started immediately in case of failure.
Parallel operation
Both pumps run simultaneously with the same set

point. The master pump determines the behavior

of the full system and is able to optimize the per-

formance. To guarantee the required performance

with the minimum power consumption, the master

pump starts or stops the second pump depending

on the head and flow that is required.

• NOTE: If an ecocirc XL basic (no communication

available) is used in parallel operation, the two

pump-heads may work in different duty points,

especially at low flow. This could create some

12

Not available on 25-40, 25-60, 32-40, 32-60 models.

en - Translation of the original instructions

24