4 change the displayed unit of measurement, 2 start or stop the pump, 1 automatic air venting procedure – Xylem ECOCIRC XL & XLplus User Manual

Page 26: 7 maintenance, 8 troubleshooting, Power speed head flow

Advertising
background image

The display will stop blinking to confirm the

change.

NOTICE:
If a non return valve is mounted on the system, it

must be ensured that the set minimum discharge

pressure of the pump is always higher than closing

pressure of the valve.

6.1.4 Change the displayed unit of
measurement

1. Press the button (3) to change the unit of

measurement. See

Figure 13

.

Power

Speed

Head

Flow

Parameter

button

Parameter

button

Parameter

button

Parameter

button

2. When flow and head are displayed, by press-

ing the button (3) for more than one second,

the unit of measurement can be changed as

follow:

• Flow: m3/h ↔ gpm (US)

• Head: m ↔ ft

6.2 Start or stop the pump

CAUTION:

• The pump must not run dry as this

can result in the destruction of the

bearings in a very short time. Fill and

vent the system correctly with liquid

before first start-up. The pump rotor

chamber will be vented after the

power on of the pump with an auto-

matic air venting procedure.

• The system cannot be vented

through the pump.

• Start the pump in one of the following ways:

• Switch on the power supply of the pump.

• Close the start/stop contact.

• Send the start command through the com-

munication bus.

The pumps starts pumping in constant pressure

mode with the following default set point:

• 2m for XX-40 models (Max head 4m)

• 3m for XX-60 models (Max head 6m)

• 4m for XX-80 models (Max head 8m)

• 5m for XX-100 models (Max head 10m)

• 6m for XX-120 models (Max head 12m)

For more information about how to change set-

ting, see

Configure the pump settings

.

• Stop the pump in one of the following ways:

• Switch off the power supply of the pump.

• Open the start/stop contact.

• Send the stop command through the com-

munication bus.

6.2.1 Automatic air venting procedure

At each power-on of the pump unit, an automatic

air venting procedure is executed. During this

phase, the user interface displays "deg" and a

count-down until the completion of the procedure.
The procedure can be recalled or skipped:

• Manually by pressing simultaneously the two

buttons (5). See

Figure 13

.

• For ecocirc XLplus only, via communication bus.

See the communication manual on www.low-

ara.com.

6.2.2 Activate automatic twin pump
operation (only for ecocirc XLplus)

The following procedure must be executed during

the start-up phase of the pump.

1. Enter the twin pump sub menu when the dis-

play is showing tuma or tusl.

2. Select the applicable twin pump operation.

• bcup = backup operation

• alte = alternative operation

• para = parallel operation

3. Push the parameter button to activate the new

setting.

The second pump is configured by the master

pump.

7 Maintenance

Precaution

Electrical Hazard:
Disconnect and lock out electrical pow-

er before installing or servicing the unit.

WARNING:

• Always wear protective gloves when

handling the pumps and motor.

When pumping hot liquids, the

pump and its parts may exceed

40°C (104°F).

• Maintenance and service must be

performed by skilled and qualified

personnel only.

• Observe accident prevention regu-

lations in force.

• Use suitable equipment and protec-

tion.

WARNING:

• A strong magnetic field is created

when the rotor is removed from or

inserted into the pump head. This

magnetic field can be harmful to

pacemaker wearers and others with

medical implants. In addition, the

magnetic field may attract metal

parts to the rotor which can cause

injuries and/or damage the bearing

of the pump.

en - Translation of the original instructions