not able to enclose the pump housing in a

diffusion-proof manner.

• If the customer creates the diffusion-proof

insulation, then the pump housing must not

be insulated above the motor flange. The

drain opening must not be obstructed so

that the accumulated condensation can run

out.

4.5 Change the position of the pump head

WARNING:

• Drain the system or close the ON-

OFF valves on both sides of the

pump before disassembling the

pump. The pumped fluid can be

pressurized and scalding hot.

• There is the risk of escaping vapor

when the pump head is separated

from the pump housing.

Electrical Hazard:
Before starting work on the unit, make

sure that the unit and the control panel

are isolated from the power supply and

cannot be energized.

CAUTION:
Burn hazard. During operation various

surfaces on the unit will become hot. To

avoid burn injury, use heat protective

gloves.

WARNING:

• A strong magnetic field is created

when the rotor is removed from or

inserted into the pump head. This

magnetic field can be harmful to

pacemaker wearers and others with

medical implants. In addition, the

magnetic field may attract metal

parts to the rotor which can cause

injuries and/or damage the bearing

of the pump.

For more information, see

Figure 14

and

Figure

15

.

1. Loosen the four hex-head screws (2) that fix

the pump head to the pump housing (4).

2. Rotate the pump head (1) in 90° steps to the

desired position.

3. When separating the pump head (1) from the

pump housing (4):

a) Avoid removing the rotor from the pump head

(1);

b) Pay attention to the magnetic hazard listed be-

fore;

c) Check that the O-ring (3) is not damaged.

A defective O-ring must be replaced. An O-

ring as spare part is already available inside

the package.

4. Fit and tighten according to the table below

for the four hex-head screws (2) that affix the

motor to the pump housing (4).

Pump model

Screw type

Torque

25–40
25–60
32–40
32–60

M5

2.0 Nm

25–80
25–100
32–80
32–100
32–100F
40–100F
50–100F

M6

10.0 Nm

32–120F
40–120F
50–80F
65–80F

M8

19.0 Nm

50–120F
65–120F
80–120F
100–120F

M10

38.0 Nm

WARNING:
check for the presence of leaks after re-

assembling the pump.

4.6 Electrical installation

Precautions

Electrical Hazard:

• Make sure that all connections are

performed by qualified installation

technicians and in compliance with

the regulations in force.

• Before starting work on the unit,

make sure that the unit and the con-

trol panel are isolated from the pow-

er supply and cannot be energized.

Grounding (earthing)

Electrical Hazard:

• Always connect the external protec-

tion conductor to ground (earth) ter-

minal before making other electrical

connections.

• All electrical equipment must be

ground (earth ) connected. This ap-

plies to the pump unit and related

equipment. Verify the pump ground

terminal is earthed.

NOTICE:
The number of power on and power off of the

pump must be less than 3 times per hour and in

any case less than 20/24h

4.6.1 Power supply connection

WARNING:

en - Translation of the original instructions

20