If the problem per-

sists, contact serv-

ice.

A02

High temperature

of the fluid

Check the correct

status of the sys-

tem

A05

Data memory cor-

rupted

Switch off the

pump for 5 mi-

nutes and then

power on. If the

problem persists,

contact service

A06

External tempera-

ture probe anom-

aly

Check the probe

and the connection

to the pump

A07

External pressure

sensor anomaly

Check the sensor

and the connection

to the pump

A12

Twin pump com-

munication lost

If both pumps

show the A12

alarm, check the

connection be-

tween the pumps.

If one of the pump

is switched off or

shows another er-

ror code, check the

section 8.1 and 8.2

to find the problem

A20

Internal alarm

Switch off the

pump for 5 mi-

nutes and then

power on. If the

problem persists,

contact service

8.4 Faults, causes, and remedies

The pump does not start

Cause

Remedy

No power.

Check the power supply

and ensure connection

to the main is intact.

Triggered ground-fault

protection device or cir-

cuit breaker.

Reset and replace blown

fuses.

Cause

Remedy

Bridged or wrong start

signal on the start/stop

contacts.

Unbridge and correct

the signal.

The pump starts but the thermal protector is trig-

gered after a short time or the fuses blow

Cause

Remedy

Damages power cable, the mo-

tor short circuits or thermal pro-

tector or fuses are not suited for

the motor current.

Check and re-

place the com-

ponents as nec-

essary.

Triggered thermo-amperomet-

ric protection (single phase) or

of the protection device (three-

phase) due to excessive current

input.

Check the pump

working condi-

tions.

Missing a phase in the power

supply.

Correct the

power supply.

The pump is making loud noises

Cause

Remedy

Not thoroughly

vented.

Recall the automatic air -

venting procedure. See sec-

tion 6.2.1 of this manual

Cavitation due to in-

sufficient suction

pressure.

Increase the system admis-

sion pressure within the ad-

missible range.

Foreign objects in

pump.

Clean the system.

Worn bearing

Contact the local sales and

service representative.

9 Other Relevant Documentation or
Manuals

9.1 Embedded Software and Driver
Software License Agreement

With the purchase of the product, the terms and

conditions of the license for the software embed-

ded on the product are considered accepted. For

more information see license condition on

www.lowara.com

1 Introduction et sécurité

1.1 Introduction

Objet de ce manuel
L'objet de ce manuel est d'apporter les informa-

tions nécessaires pour :

• L'installation

• L'utilisation

• La maintenance

ATTENTION :
Lire attentivement ce manuel avant

d'installer et d'utiliser ce produit. Une

mauvaise utilisation du produit peut en-

traîner des blessures et des dégâts ma-

tériels et pourrait annuler la garantie.

REMARQUE :

fr - Traduction des instructions d'origine

28

Advertising