2 minimum inlet pressure at the suction port, 3 piping requirements, 3 electrical requirements – Xylem ECOCIRC XL & XLplus User Manual

Page 19: 4 pump installation

Advertising
background image

Guidelines
Observe the following guidelines regarding the lo-

cation of the product:

• Make sure that the installation area is protected

from any fluid leaks, or flooding.

• If possible, place the pump slightly higher than

the floor level.

• Provide shut-off valves in front of and behind

the pump.

• The relative humidity of the ambient air must be

less than 95%.

4.2.2 Minimum inlet pressure at the
suction port

The values in the table are the inlet pressure above

the atmospheric pressure.

Nominal

Diameter

Fluid tem-

perature

25°C

Fluid tem-

perature

95°C

Fluid tem-

perature

110°C

RP 1

0.2 bar

1 bar

1.6 bar

RP 1 ¼

0.2 bar

1 bar

1.6 bar

DN 32

0.3 bar

1.1 bar

1.7 bar

DN 40

0.3 bar

1.1 bar

1.7 bar

DN 50

0.3 bar

1.1 bar

1.7 bar

DN 65

0.5 bar

1.3 bar

1.9 bar

DN 80

0.5 bar

1.3 bar

1.9 bar

DN 100

0.5 bar

1.3 bar

1.9 bar

NOTICE:

• Do not apply a pressure lower than the values

specified as this could cause cavitation and

damage the pump.

• The inlet pressure plus the pump pressure

against a closed valve must be lower than maxi-

mum admissible system pressure.

4.2.3 Piping requirements

Precautions

WARNING:

• Use pipes suited to the maximum

working pressure of the pump. Fail-

ure to do so can cause the system to

rupture, with the risk of injury.

• Make sure that all connections are

performed by qualified installation

technicians and in compliance with

the regulations in force.

• Do not use the on-off valve on the

discharge side in the closed position

for more than a few seconds. If the

pump must operate with the dis-

charge side closed for more than a

few seconds, a bypass circuit must

be installed to prevent overheating

of the water inside the pump.

Piping checklist

• Pipes and valves must be correctly sized.

• Pipe work must not transmit any load or torque

to pump flanges.

4.3 Electrical requirements

• The local regulations in force overrule specified

requirements listed below.

Electrical connection checklist
Check that the following requirements are met:

• The electrical leads are protected from high

temperature, vibrations, and collisions.

• The current type and voltage of mains connec-

tion must correspond to the specifications on

the data plate on the pump.

• The power supply line is provided with:

• A high-sensitivity differential switch (30 mA)

[residual current device RCD] suitable for

earth fault currents with DC or pulsating DC

content (a Type B RCD is suggested).

• A mains isolator switch with a contact gap of

at least 3 mm

The electrical control panel checklist

NOTICE:
The control panel must match the ratings of the

electric pump. Improper combinations could fail to

guarantee the protection of the unit.

Check that the following requirements are met:

• The control panel must protect the pump

against short-circuit. A time lag fuse or a circuit

breaker (Type C model is suggested) can be

used to protect the pump.

• The pump has built in overload and thermal

protection, no additional overload protection is

required.

The motor checklist
Use cable according to rules with 3 leads (2 +

earth/ground). All cable must be heat-resistant up

to +85°C (185°F).

4.4 Pump installation

1. Install the pump according to the systems liq-

uid flow.

• The arrow on the pump housing shows the

flow direction through the pump.

• The pump must be installed with the pump

head in a horizontal position. For more in-

formation about allowed positions, see

Fig-

ure 12

2. If necessary, rotate the position of the pump

head for better reading of the user interface.
For more instructions, see

Change the position

of the pump head

.

3. If applicable, install the thermal shells.

• Only use the pump thermal shells that are

included in the delivery. Do not insulate the

motor housing, the electronics can over-

heat so that the pump automatically switch

off.

• The thermal shells that are included in the

delivery must only be used in hot water cir-

culation applications with fluid temperature

above 20°C (68°F). The thermal shells are

en - Translation of the original instructions

19