Be aware that running the motor at a low speed for a long time can cause motor
overheating. This is particularly true when manual torque boost is ON, or if the motor
relies on a built-in fan for cooling.

Voltage gain – Using parameter A045 you can
modify the voltage gain of the inverter (see
graph at right). This is specified as a
percentage of the full scale output voltage.
The gain can be set from 20% to 100%. It
should be adjusted in accordance with the
motor specifications.

The following table shows the methods of
torque control selection.

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Torque boost select

A041

V-Bst Slct

MN

U

00

00

%

Torque boost select, 2

nd

motor

A241

2VBst Slct

MN

Two options:
00

}Manual torque boost

01

}Automatic torque boost

U

00

00

%

Manual torque boost value

A042

V-Bst V

0005.0%

9

1.8

1.8

%

Manual torque boost value,
2

nd

motor

A242

2VBst V

0005.0%

Can boost starting torque
between 0 and 20% above normal
V/f curve,
range is 0.0 to 20.0%

9

0.0

0.0

%

Manual torque boost
frequency adjustment

A043

M-Bst F

0003.0%

9

10.0

10.0

%

Manual torque boost
frequency adjustment,
2nd motor

A243

2MBst F

0000.0%

Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque boost,
range is 0.0 to 50.0%

9

0.0

0.0

%

V/f characteristic curve

A044

CTRL

C-TRQ

U

00

00



V/f characteristic curve,
2nd motor

A244

2CTRL

C-TRQ

Two available V/f curves;
00

}Constant torque

01

}Reduced torque

06

}Reduced torque1

U

00

00



V/f gain setting

A045

V-Gain

00100%

9

100.

100.

%

V/f gain setting,
2nd motor

A245

2V-Gain

00100%

Sets voltage gain of the inverter,
range is 20. to 100.%

9

100.

100.

%

100%

fbase

fmax

A045=100

80%

A045=80

V

0

3

17

3

−17