Dc bus avr for deceleration settings – XLT Hitachi X200 User Manual

Page 129

Advertising
background image

DC Bus AVR for Deceleration Settings

This function is to achieve stable DC
bus voltage in case of deceleration. DC
bus voltage rises due to regeneration
during deceleration. When this
function is activated (B133=01),
inverter controls the deceleration time
so that the DC bus voltage not to go up
to the overvoltage trip level, and leads
to the trip-less operation during
deceleration.

Please note that the actual
deceleration time may be longer in this
case.

“B” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

DC bus AVR for decel.

P-gain

B055

VpnP

0000.2s

Proportional gain adjustment for
DC bus AVR function. Range is:
0.2 to 5.0

9

0.2

0.2



DC bus AVR for decel.

I-time

B056

VpnI

0000.2s

Integration time adjustment for
DC bus AVR function. Range is:
0.0 to 150.0

9

0.2

0.2

sec

DC bus AVR selection

B133

Vpn AVR

OFF

00

}Disabled

01

}Enabled

U

00

00



Threshold voltage of DC bus
AVR setting

B134

Vpn LVL

00380V

Setting of threshold voltage of
DC bus voltage to start DC bus
AVR function. Range is:
200V class

}330 to 395

400V class

}660 to 790

U

380

/760

380

/760

V

Difference between OV LAD STOP and DC bus AVR

This function is similar to OV LAD STOP (B130,B131) from the OV trip-less point of view.
The DC bus AVR has the higher priority when both OV LAD STOP function and DC bus AVR
function is set enabled.

OV LAD STOP

DC bus AVR

Actual deceleration time

Short

Long

Fluctuation of the DC bus voltage

Big

Small

Please select the suitable function according to your system.

Threshold voltage to start DC bus AVR (B134)

DC bus AVR

t

t

DC bus voltage

Freq

Normal

operation

Config

uri
ng Driv

e

Parameters

3

46

3

−46

&RQ¿JXULQJ'ULYH

Parameters

Advertising