List of Coil Numbers

Coil

Number

Name

R/W

Description

0014h

Alarm signal

R

0…Normal
1…Trip

0015h

PID deviation signal

R

0016h

Overload signal

R

0017h

Frequency arrival signal
(set frequency or above)

R

0018h

Frequency arrival signal
(at constant speed)

R

0019h

Run Mode signal

R

0…OFF
1…ON

001Ah

Data writing

R

0…Normal status
1…Writing

001Bh

CRC error

R

001Ch

Overrun error

R

001Dh

Framing error

R

001Eh

Parity error

R

001Fh

Check sum error

R

0…No error *2
1…Error

Note 1:

ON usually when either the control circuit terminal board or a coil is ON.
Among control circuit terminal board (intelligent input terminals) and coils,
the control circuit terminal board has a high priority. If the master cannot
reset the coil ON status due to a transmission line break, please turn ON and
OFF the control circuit terminal board to make the coil to OFF status.

Note 2:

The content of a transmission error is held until the error is reset. (The error
can be reset while the inverter is running.)

B

20

Appe

ndix B

B

−20

Appendix B