The data set in the response is as follows:

Response Buffer

4-5

6-7

8-9

Register Number

12+0 (high

order)

12+0

(low

order)

12+1

(high

order)

12+1 (low

order)

12+2

(high

order)

12+2 (low

order)

Register Data

0003h

00h

00h

0063h

Trip data

Trip factor (E03)

Not used

Frequency (9.9Hz)

Response Buffer

10-11

12-13

14-15

Register Number

12+3 (high

order)

12+3

(low

order)

12+4

(high

order)

12+4 (low

order)

12+5

(high

order)

12+5 (low

order)

Register Data

00h

00h

001Eh

011Ch

Trip data

Not used

Output current (3.0A)

DC-bus voltage (284V)

When the Read Holding Register command cannot be executed normally, refer to the
exception response.

Write in Coil [05h]:

This function writes data in a single coil. Coil status changes are as follows:

Coil Status

Data

OFF to ON

ON to OFF

Change data (high order)

FFh

00h

Change data (low order)

00h

00h

An example follows (note that to command the inverter, set A002=03):

x Sending a RUN command to an inverter having slave address “8”

x This example writes in coil number “1.”

Query:

Response:

No.

Field Name

Example

(Hex)

No.

Field Name

Example

(Hex)

1

Slave address *1

08

1

Slave address

08

2

Function code

05

2

Function code

05

3

Coil start address *2
(high order)

00

3

Coil start address *2
(high order)

00

4

Coil start address *2
(low order)

00

4

Coil start address *2
(low order)

00

5

Change data
(high order)

FF

5

Change data
(high order)

FF

6

Change data
(low order)

00

6

Change data
(low order)

00

7

CRC-16 (high order)

8C

7

CRC-16 (high order)

8C

8

CRC-16 (low order)

A3

8

CRC-16 (low order)

A3

Note 1:

No response is made for a broadcasting query.

Note 2:

The PDU Coils are addressed starting at zero. Therefore coils numbered 1-31
are addressed as 0-30. Coil address value (transmitted on Modbus line) is 1
less than the Coil Number.

When writing in a selected coil fails, see the exception response.

B

12

Appe

ndix B

B

−12

Appendix B