Set second motor, special set – XLT Hitachi X200 User Manual

Page 165

Advertising
background image

Set Second Motor, Special Set

If you assign the [SET] function to an intelligent input terminal, you can select between
two sets of motor parameters. The second parameters store an alternate set of motor
characteristics. When the terminal [SET] is turned ON, the inverter will use the second
set of parameters to generate the frequency output to the motor. When changing the
state of the [SET] input terminal, the change will not take effect until the inverter is
stopped. Special Set [SP-SET] is for changing the second motor parameters without
stopping the motor. However the changeable parameters are limited.

When you turn ON the [SET] input, the inverter operates per the second set of
parameters. When the terminal is turned OFF, the output function returns to the
original settings (first set of motor parameters). Refer to

“Configuring the Inverter for

Multiple Motors” on page 4–58

for details.

Parameters

SET

SP-SET

Parameters

SET

SP-SET

F002/F202

9

9

A093/A293

9

9

F003/F203

9

9

A094/A294

9

9

A001/A201

9

-

A095/A295

9

9

A002/A202

9

-

A096/A296

9

9

A003/A203

9

-

b012/b212

9

-

A004/A204

9

-

b013/b213

9

-

A020/A220

9

9

b021/b221

9

-

A041/A241

9

-

b022/b222

9

-

A042/A242

9

9

b023/b223

9

-

A043/A243

9

9

b028/b228

9

-

A044/A244

9

-

A045/A245

9

-

C001~C005/
C201~C205

9

-

A061/A261

9

9

C041/C241

9

-

A062/A262

9

9

H003/H203

9

-

A092/A292

9

9

H004/H204

9

-

H006/H206

9

-

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

causes the inverter to use the 2nd set of motor
parameters for generating the frequency output to
motor

08

53

SET

SP-SET

Set (select) 2nd
Motor data

Set 2nd motor data
Special SET

OFF

causes the inverter to use the 1st (main) set of
motor parameters for generating the frequency
output to motor

Valid for inputs:

C001~C005

Required settings

(none)

Notes:
x If the terminal state is changed while the

inverter is running, the inverter continues using
the current set of parameters until the inverter
is stopped.

Example (requires input configuration—see

page 3–49

):

See I/O specs on

page 4–6.

5

4

3

2

1

L PCS P24

SET / SP-SET

4

16

Operations and

Monitori

ng

4

−16

Operations and

Monitoring

Advertising