XLT Hitachi X200 User Manual

Page 138

Advertising
background image

Output Function Summary Table – This table shows all twelve functions for the logical
outputs (terminals [11] and [AL]) at a glance. Detailed descriptions of these functions,
related parameters and settings, and example wiring diagrams are in

“Using Intelligent

Output Terminals” on page 4-34

.

Output Function Summary Table

Option

Code

Terminal

Symbol

Function Name

Description

ON

When the inverter is in Run Mode

00

RUN

Run Signal

OFF

When the inverter is in Stop Mode

ON

When output to motor is at the set frequency

01

FA1

Frequency Arrival Type
1–Constant Speed

OFF

When output to motor is OFF, or in any
acceleration or deceleration ramp

ON

When output to motor is at or above the set
frequency, even if in accel. or decel rams

02

FA2

Frequency Arrival Type
2–Over frequency

OFF

When output to motor is OFF, or at a level
below the set frequency

ON

When output current is more than the set
threshold for the overload signal

03

OL

Overload Advance
Notice Signal

OFF

When output current is less than the set
threshold for the deviation signal

ON

When PID error is more than the set threshold
for the deviation signal

04

OD

Output Deviation for
PID Control

OFF

When PID error is less than the set threshold
for the deviation signal

ON

When an alarm signal has occurred and has not
been cleared

05

AL

Alarm Signal

OFF

When no alarm has occurred since the last
cleaning of alarm(s)

ON

When the [O] input value < B082 setting (signal
loss detected), or the [OI] input current < 4mA

06

Dc

Analog Input
Disconnect Detect

OFF

When no signal loss is detected

ON

Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is less
than the Feedback Low Limit (C053)

07

FBV

PID Second Stage
Output

OFF

Transitions to OFF when the PID Process
Variable (PV) exceeds the PID High Limit
(C052), and transitions to OFF when the
inverter goes from Run Mode to Stop Mode

ON

When the communications watchdog timer
(period specified by C077) has time out

08

NDc

Network Detection
Signal

OFF

When the communications watchdog timer is
satisfied by regular communications activity

ON

When the Boolean operation specified by C143
has a logical “1” result

09

LOG

Logic Output Function

OFF

When the Boolean operation specified by C143
has a logical “0” result

ON

No communication between communication
option is detected during a time set in P044

10

ODc

Communication option
error

OFF

Communication is normal

ON

Motor current is less than the set value of C039

43

LOC

Low load detection

OFF

Motor current is not less than the set value of
C039

3

55

Config

uri

ng Driv

e

Parameters

3

−55

&RQ¿JXULQJ'ULYH

Parameters

Advertising