Unattended start protection – XLT Hitachi X200 User Manual

Page 169

Advertising
background image

Unattended Start Protection

If the Run command is already set when power is turned ON, the inverter starts
running immediately after powerup. The Unattended Start Protection (USP) function
prevents that automatic startup, so that the inverter

will not

run without outside

intervention. When USP is active and you need to reset an alarm and resume running,
either turn the Run command OFF, or perform a reset operation by the terminal [RS]
input or the keypad Stop/reset key.

In the figure below, the [USP] feature is enabled. When the inverter power turns ON,
the motor does not start, even though the Run command is already active. Instead, it
enters the USP trip state, and displays E13 error code. This requires outside
intervention to reset the alarm by turning OFF the Run command per this example (or
applying a reset). Then the Run command can turn ON again and start the inverter
output.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

On powerup, the inverter will not resume a Run
command (mostly used in the US)

13

USP

Unattended Start
Protection

OFF

On powerup, the inverter will resume a Run
command that was active before power loss

Valid for inputs:

C001~C005

Required settings

(none)

Notes:
x Note that when a USP error occurs and it is

canceled by a reset from a [RS] terminal input,
the inverter restarts running immediately.

x Even when the trip state is canceled by turning

the terminal [RS] ON and OFF after an under
voltage protection E09 occurs, the USP function
will be performed.

x When the running command is active

immediately after the power is turned ON, a
USP error will occur. When this function is
used, wait for at least three (3) seconds after the
powerup to generate a Run command.

Example (default input configuration shown for
–FU models; –FE and –FR models require input
configuration—see

page 3–49

):

See I/O specs on

page 4–6.

5

4

3

2

1

L PCS P24

USP

Inverter output frequency

0

t

Inverter power supply

1

0

Alarm output terminal

1

0

[USP] terminal

1

0

Run command [FW,RV]

1

0

Events:

E13

Alarm

cleared

Run

command

4

20

Operations and

Monitori

ng

4

−20

Operations and

Monitoring