XLT Hitachi X200 User Manual

Page 173

Advertising
background image

Thermistor Thermal Protection

Motors that are equipped with a thermistor can be protected from overheating. Input
terminal [5] has the unique ability to sense a thermistor resistance. When the
resistance value of the thermistor connected to terminal [TH] (5) and [L] is more than
3 k

Ÿ ±10%, the inverter enters the Trip Mode, turns OFF the output to the motor, and

indicates the trip status E35. Use this function to protect the motor from overheating.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

When a thermistor is connected to terminals [5]
and [L], the inverter checks for over-temperature
and will cause trip (E35) and turn OFF the output
to the motor

19

TH

Thermistor Thermal
Protection

OFF

An open circuit in the thermistor causes a trip,
and the inverter turns OFF the output

Valid for inputs:

C005 only

Required settings

(none)

Notes:
x Be sure the thermistor is connected to terminals

[5] and [L]. If the resistance is above the
threshold the inverter will trip. When the motor
cools down enough, the thermistor resistance
will change enough to permit you to clear the
error. Press the STOP/Reset key to clear the
error.

Example (requires input configuration—
see

page 3–49

):

NOTE: The trip level is hardware wise fixed and cannot be changed.

4

3

2

1

L PCS P24

TH

thermistor

Motor

5

4

24

Operations and

Monitori

ng

4

−24

Operations and

Monitoring

Advertising