PID Control

When enabled, the built-in PID loop calculates an ideal inverter output value to cause a
loop feedback process variable (PV) to move closer in value to the set point (SP). The
frequency command serves as the SP. The PID loop algorithm will read the analog input
for the process variable (you specify the current or voltage input) and calculate the
output.

x

A scaled factor in A075 lets you multiply the PV factor, converting it into
engineering units for the process.

x

Proportional, integral, and derivative gains are all adjustable.

x

See “

PID Loop Operation” on page 4-56

for more information.

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

PID enable

A071

PID Mode

OFF

Enables PID function,
two option codes:
00

}PID Disable

01

}PID Enable

U

00

00



PID proportional gain

A072

PID P

0001.0

Proportional gain has a range of
0.2 to 5.0

9

1.0

1.0



PID integral time constant

A073

PID I

0001.0s

Integral time constant has a
range of 0.0 to 150 seconds

9

1.0

1.0

sec

PID derivative time constant

A074

PID D

000.00s

Derivative time constant has a
range of 0.0 to 100 seconds

9

0.00

0.00

sec

PV scale conversion

A075

PID Cnv

001.00%

Process Variable (PV), scale
factor (multiplier), range of 0.01
to 99.99

U

1.00

1.00



PV source setting

A076

PID INP

OI

Selects source of Process Variable
(PV), option codes:
00

}[OI] terminal (current in)

01

}[O] terminal (voltage in)

02

}ModBus network

10

}Calculate function output

U

00

00



Reverse PID action

A077

PID MINUS

OFF

Two option codes:
00

}PID input = SP-PV

01

}PID input = -(SP-PV)

U

00

00



PID output limit

A078

PID Vari

0000.0%

Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0%

U

0.0

0.0

%

NOTE: The setting A073 for the integrator is the integrator’s time constant Ti, not the
gain. The integrator gain Ki = 1/Ti. When you set A073 = 0, the integrator is disabled.