List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

A092

(high)

R/W

1074h

A092

(low)

Acceleration (2) time
setting

R/W

Duration of 2nd segment of
acceleration, range is:
0.01 to 3000 sec.

1075h

1 to

300000

*1

0.01 sec

A292

(high)

R/W

1519h

A292

(low)

Acceleration (2) time
setting,
2nd motor

R/W

Duration of 2nd segment of
acceleration, 2nd motor, range is:
0.01 to 3000 sec.

151Ah

1 to

300000

*1

0.01 sec

A093

(high)

R/W

1076h

A093

(low)

Deceleration (2) time
setting

R/W

Duration of 2nd segment of
deceleration, range is:
0.01 to 3000 sec.

1077h

1 to

300000

*1

0.01 sec

A293

(high)

R/W

151Bh

A293

(low)

Deceleration (2) time
setting,
2nd motor

R/W

Duration of 2nd segment of
deceleration, 2nd motor, range is:
0.01 to 3000 sec.

151Ch

1 to

300000

*1

0.01 sec

A094

Select method to
switch to Acc2/Dec2
profile

R/W Two options for switching from

1st to 2nd accel/decel:
00

}2CH input from terminal

01

}Transition frequency

1078h

A294

Select method to
switch to Acc2/Dec2
profile, 2nd motor

R/W Two options for switching from

1st to 2nd accel/decel:
00

}2CH input from terminal

01

}Transition frequency

(2nd motor)

151Dh

0, 1



A095

Acc1 to Acc2 frequency
transition point

R/W Output frequency at which

Accel1 switches to Accel2, range
is 0.0 to 400.0 Hz

107Ah

A295

Acc1 to Acc2 frequency
transition point, 2nd
motor

R/W Output frequency at which

Accel1 switches to Accel2, 2nd
motor, range is 0.0 to 400.0 Hz

151Fh

0 to 4000

0.1 Hz

A096

Dec1 to Dec2 frequency
transition point

R/W Output frequency at which

Decel1 switches to Decel2, range
is 0.0 to 400.0 Hz

107Ch

A296

Dec1 to Dec2 frequency
transition point, 2nd
motor

R/W Output frequency at which

Decel1 switches to Decel2, 2nd
motor, range is 0.0 to 400.0 Hz

1521h

0 to 4000

0.1 Hz

A097

Acceleration curve
selection

R/W Set the characteristic curve of

Acc1 and Acc2, two options:
00

}linear

01

}S-curve

107Dh

0, 1



A098

Deceleration curve
selection

R/W Set the characteristic curve of

Dec1 and Dec2, two options:
00

}linear

01

}S-curve

107Eh

0, 1



A101

[OI]-[L] input active
range start frequency

R/W The output frequency

corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz

1080h

0 to 4000

0.1 Hz

A102

[OI]-[L] input active
range end frequency

R/W The output frequency

corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz

1082h

0 to 4000

0.1 Hz

A103

[OI]-[L] input active
range start current

R/W The starting point (offset) for the

current input range,
range is 0. to 100.%

1083h

0 to 100

1 %