B089: Monitor display select for networked inverter – When the X200 inverter is
controlled via network, the inverter’s keypad display can still provide Monitor Mode.
The D00x parameter selected by function B089 will be displayed on the keypad. See

“Local Monitoring During Network Operation” on page 3-8

for more details.

B092: Cooling Fan Control – You can select the performance of the cooling fan (if your
inverter model includes a fan). This function controls whether the cooling fan stops or
keeps on running after the inverter stops the motor. This can result in an additional
energy saving and extends fan life.

“B” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Monitor display select for
networked inverter

B089

PANEL

d001

Selects the parameter displayed on the
keypad display when the inverter is
networked, 7 options:
01

}Output frequency monitor

02

}Output current monitor

03

}Rotation direction monitor

04

}Process variable (PV), PID

feedback monitor

05

}Intelligent input terminal status

06

}Intelligent output terminal status

07

}Scaled output frequency monitor

9

01

01



Cooling fan control

B092

FAN-CTRL

OFF

Selects when the fan is ON during
inverter operation, three options:
00

}Fan is always ON

01

}Fan is ON during run, OFF during

stop (5 minute delay from ON to
OFF)

02

}Fan is temperature controlled

U

00

00



3

44

Config

uri
ng Driv

e

Parameters

3

−44

&RQ¿JXULQJ'ULYH

Parameters