ModBus Data Listing

ModBus Coil List

The following tables list the primary coils for the inverter interface to the network. The
table legend is given below.

x Coil Number - The network

register address offset

for the coil. The coil data is a

single bit (binary) value.

x Name - The functional name of the coil

x R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data

x Description - The meaning of each of the states of the coils

List of Coil Numbers

Coil

Number

Name

R/W

Description

0000h

(Reserved)

R



0001h

Run command

R/W

0…Stop
1…Run (enable when A003=03)

0002h

FW/RV command

R/W

0…RV
1…FW (enable when A003=03)

0003h

External trip (EXT)

R/W

0…No trip event
1…Trip occurred

0004h

Trip reset (RS)

R/W

0…No reset condition
1…Reset

0005h

(Reserved)

R



0006h

(Reserved)

R



0007h

Intelligent input terminal 1

R/W

0008h

Intelligent input terminal 2

R/W

0009h

Intelligent input terminal 3

R/W

000Ah

Intelligent input terminal 4

R/W

000Bh

Intelligent input terminal 5

R/W

0…OFF *1
1…ON

000Dh

(Not used)





000Eh

Run/Stop status

R

0…Stop (corresponds to D003 monitor)
1…Run

000Fh

FW/RV status

R

0…FW
1…RV

0010h

Inverter ready

R

0…Not ready
1…Ready

0011h

(Reserved)

R



0012h

(Reserved)

R



0013h

(Reserved)

R