Analog Input Calculate Function – The inverter can mathematically combine two input
sources into one value. The Calculate function can either add, subtract, or multiply the
two selected sources. This provides the flexibility needed by various applications. You
can use the result for the output frequency setting (use A001=10) or for the PID Process
Variable (PV) input (use A075=03).

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

A input select for calculate
function

A141

CALC Slct1

POT

Five options:
00

}Digital operator

01

}Keypad potentiometer

02

}[O] input

03

}[OI] input

04

}Network variable

U

01

01



B input select for calculate
function

A142

CALC Slct2

OI

Five options:
00

}Digital operator

01

}Keypad potentiometer

02

}[O] input

03

}[OI] input

04

}Network variable

U

02

02



Calculation symbol

A143

CALC SMBL

Calculates a value based on the A
input source (A141 selects) and B
input source (A142 selects).
Three options:
00

}ADD (A input + B input)

01

}SUB (A input - B input)

02

}MUL (A input * B input)

U

00

00



NOTE: For A141 and A142, it is not possible to use [O] and [OI] together in calculation,
because using both inputs at the same time on the X200 series inverter is not allowed.

Digital operator

Potentiometer

[O] input

[OI] input

Network variable

A141

A input select

A142

B input select

x A + B
x A - B

x A * B

A

B

A143

Digital operator

Potentiometer

[O] input

[OI] input

Network variable

“CAL”
(result)

3

29

Config

uri
ng Driv

e

Parameters

3

−29

&RQ¿JXULQJ'ULYH

Parameters