XLT Hitachi X200 User Manual

Page 179

Advertising
background image

Add Frequency Enable

The inverter can add or subtract an offset value to the output frequency setting which is
specified by A001 (will work with any of the five possible sources). The ADD Frequency
is a value you can store in parameter A145. The ADD Frequency is summed with or
subtracted from the output frequency setting only when the [ADD] terminal is ON.
Function A146 selects whether to add or subtract. By configuring an intelligent input as
the [ADD] terminal, your application can selectively apply the fixed value in A145 to
offset (positively or negatively) the inverter output frequency in real time.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Applies the A145 Add Frequency value to the
output frequency

50

ADD

ADD Frequency
Enable

OFF

Does not apply the Add frequency. The output
frequency retains its normal value

Valid for inputs:

C001~C005

Required settings

A001, A145, A146

Notes:
x A001 may specify any source; the Add

Frequency will be added to or subtracted from
that value to yield output frequency value.

Example (default input configuration shown—see

page 3–49

):

See I/O specs on

page 4–6.

Keypad potentiometer

Control terminal

Function F001 setting

ModBus network input

Calculate function output

Ȉ

+

A001

Frequency source setting

Output frequency setting

A145 ADD frequency

A146

ADD direction select

+/-

Intelligent input

[ADD]

5

4

3

2

1

L PCS P24

ADD

4

30

Operations and

Monitori

ng

4

−30

Operations and

Monitoring