Frequency-related Functions

Frequency Limits – Upper and lower
limits can be imposed on the inverter
output frequency. These limits will
apply regardless of the source of the
speed reference. You can configure the
lower frequency limit to be greater than
zero as shown in the graph. The upper
limit must not exceed the rating of the
motor or capability of the machinery.
The maximum frequency setting
(A004/A204) takes precedence over
frequency upper limit (A061/A261).

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Frequency upper limit setting

A061

Lim H

0000.0Hz

Sets a limit on output frequency
less than the maximum
frequency (A004).
Range is from frequency lower
limit (A062) to maximum
frequency (A004).
0.0 setting is disabled
>0.0 setting is enabled

U

0.0

0.0

Hz

Frequency upper limit
setting, 2nd motor

A261

2Lim H

0000.0Hz

Sets a limit on output frequency
less than the maximum
frequency (A204).
Range is from frequency lower
limit (A262) to maximum
frequency (A204).
0.0 setting is disabled
>0.0 setting is enabled

U

0.0

0.0

Hz

Frequency lower limit setting

A062

Lim L

0000.0Hz

Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled

U

0.0

0.0

Hz

Frequency lower limit
setting, 2nd motor

A262

2Lim L

0000.0Hz

Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled

U

0.0

0.0

Hz

Output

frequency

A061

Upper

limit

Settable

range

A062

Lower

limit

Frequency command

0

3

20

Config

uri

ng Driv

e

Parameters

3

−20

&RQ¿JXULQJ'ULYH

Parameters