The following table lists holding registers for the “D” Group Monitor Functions.

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

D001

Output frequency
monitor

R

Real-time display of output
frequency to motor, from 0.0 to
400.0 Hz

1002h

0 to 4000

0.1 Hz

D002

Output current
monitor *1

R

Filtered display of output
current to motor (100 ms
internal filter time constant),
range is 0 to 200% of inverter
rated current

1003h

0 to 2000

0.1%

D003

Rotation direction
monitor

R

Three different indications:
00...Stop
01...Forward
02...Reverse

1004h

0,1,2



D004

(high)

R

1005h

D004

(low)

Process Variable (PV),
PID feedback monitor

R

Displays the scaled PID process
variable (feedback) value (A075
is scale factor), range is 0.00 to
9999.00

1006h

0 to

999900

0.00%

times

const.

D005

Intelligent input
terminal status

R

Displays the state of the
intelligent input terminals [x],
Bit 0 = [1] to Bit 4 = [5]

1007h

0 to 63



D006

Intelligent output
terminal status

R

Displays the state of the
intelligent output terminals [x],
Bit 0 = [11], Bit 1 = (Don’t Care),
Bit 2 = [AL]

1008h

0 to 7



D007

(high)

R

1009h

D007

(low)

Scaled output
frequency monitor

R

Displays the output frequency
scaled by the constant in B086.
Decimal point indicates range:
0.00 to 39960.00

100Ah

0 to

3996000

0.01 Hz

times

const.

D013

Output voltage
monitor

R

Voltage of output to motor, range
is 0.00 to 200.00%

100Ch

0 to

20000

0.01%

D016

(high)

R

100Eh

D016

(low)

Cumulative operation
RUN time monitor

R

Displays total time the inverter
has been in RUN mode in hours.
Range is 0 to 999999

100Fh

0 to

999999

1 hour

D017

(high)

R

1010h

D017

(low)

Cumulative power-on
time monitor

R

Displays total time the inverter
has been in RUN mode in hours.
Range is 0 to 999999

1011h

0 to

999999

1 hour

D018

Fin temperature
monitor

R

Display the Fin temperature in
0.0~200.0

qC

116Ah

0 to 2000

0.1

qC

D080

Trip counter

R

Number of trip events, range is 0
to 65535

0011h

0 to 65535

1 trip
event

D102

DC voltage monitor

R

Voltage of DC bus inside
inverter,Range is 0.0 to 999.9

116Ch

0 to 9999

0.1 V

D104

Electronic thermal
monitor

R

Accumulated value of electronic
thermal detection, range is from
0.0 to 100.0

116Dh

0 to 1000

0.1 %

Note 1:

Assume that the inverter current rating is 1000 (for D002).