The following table lists the holding registers for the “C” Group Intelligent Input Functions.

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

C001

Terminal [1] function

R/W

1103h

C201

Terminal [1] function,
2nd motor

R/W

1532h

C002

Terminal [2] function

R/W

1104h

C202

Terminal [2] function,
2nd motor

R/W

1533h

C003

Terminal [3] function

R/W

1105h

C203

Terminal [3] function,
2nd motor

R/W

1534h

C004

Terminal [4] function

R/W

1106h

C204

Terminal [4] function,
2nd motor

R/W

1535h

C005

Terminal [5] function

R/W

1107h

C205

Terminal [5] function,
2nd motor

R/W

See “Input Terminal Configuration”

on page 3-49

1536h

0, 1, 2, 3,
4, 5, 6, 7,

8, 9, 11,

12, 13,
15, 16,
18, 19,
20, 21,
22, 23,
24, 27,
28, 29,
31, 50,
51, 52,
53, 64,

255



C011

Terminal [1] active state

R/W

110Bh

0, 1



C012

Terminal [2] active state

R/W

110Ch

0, 1



C013

Terminal [3] active state

R/W

110Dh

0, 1



C014

Terminal [4] active state

R/W

110Eh

0, 1



C015

Terminal [5] active state

R/W

Select logic conversion, two option
codes:
00

}normally open [NO]

01

}normally closed [NC]

110Fh

0, 1



C021

Terminal [11] function

R/W

1114h



C026

Alarm relay terminal
function

R/W

See “Output Terminal

Configuration” on page 3-54

1119h

0, 1, 2, 3,
4, 5, 6, 7,

8, 9, 10,

43



C028

[AM] signal selection

R/W Two available functions:

00

}motor speed

01

}motor current

111Bh

0, 1



C031

Terminal [11] active
state

R/W Select logic conversion:

00

}normally open [NO]

01

}normally closed [NC]

111Dh

0, 1



C036

Alarm relay active state

R/W Select logic conversion:

00

}normally open [NO]

01

}normally closed [NC]

1122h

0, 1



C038

Output mode of low load
detection signal

R/W Three option codes:

00

}Disabled

01

}During acceleration,

deceleration and constant speed

02

}During constant speed only

1178h

0, 1, 2



C039

Low load detection level

R/W Set the level of low load detection,

range is 0.0 to 2.0*rated current

1179h

0 to

20000

0.01%

C041

Overload level setting

R/W

1124h

C241

Overload level setting,
2nd motor

R/W

Sets the overload signal level
between 0% and 200% (from 0 to two
time the rated current of the
inverter)

153Ah

0 to

20000

0.01%

C042

Frequency arrival
setting for acceleration

R/W Sets the frequency arrival setting

threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz

1126h 0 to 4000

*1

0.1 Hz

C043

Frequency arrival
setting for deceleration

R/W Sets the frequency arrival setting

threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz

1128h 0 to 4000 0.1 Hz

B

36

Appe

ndix B

B

−36

Appendix B