XLT Hitachi X200 User Manual

Page 142

Advertising
background image

“C” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Overload level setting

C041

OV LVL

001.60A

Sets the overload signal level
between 0% and 200% (from 0 to
two time the rated current of the
inverter)

U

Rated current

for each

inverter model

A

Overload level setting,
2nd motor

C241

2OV LVL

001.60A

Sets the overload signal level
between 0% and 200% (from 0 to
two time the rated current of the
inverter)

U

Rated current

for each

inverter model

A

Frequency arrival setting
for acceleration

C042

ARV ACC

0000.0Hz

Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

Frequency arrival setting
for deceleration

C043

ARV DEC

0000.0Hz

Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

PID deviation level setting

C044

ARV PID

003.0%

Sets the allowable PID loop error
magnitude (absolute value), SP-PV,
range is 0.0 to 100%

U

3.0

3.0

%

PID FBV function high
limit

C052

PID LtU

0100.0%

When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0 to
100%

U

100.0 100.0

%

PID FBV function variable
low limit

C053

PID LtL

0000.0%

When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%

U

0.0

0.0

%

3

59

Config

uri

ng Driv

e

Parameters

3

−59

&RQ¿JXULQJ'ULYH

Parameters

Advertising