Output terminal configuration – XLT Hitachi X200 User Manual

Page 137

Advertising
background image

Output Terminal Configuration

The inverter provides configuration for logic (discrete) and analog outputs, shown in the
table below.

“C” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Terminal [11] function

C021

OUT-TM 11

FA1

12 programmable functions available
for logic (discrete) outputs
(see next section)

U

01

[FA1]

01

[FA1]



Alarm relay terminal
function

C026

OUT-TM RY

AL

12 programmable functions available
for logic (discrete) outputs
(see next section)

U

05

[AL]

05

[AL]



AM signal selection

C028

AM-KIND

F

Two available functions:
00

}motor speed

01

}motor current

(see after next section)

U

00

[freq]

00

[freq]

The output logic conversion is programmable for terminal [11] and the alarm relay
terminal. The open-collector output terminal [11] defaults to normally open (active low),
but you can select normally closed (active high) for the terminal in order to invert the
sense of the logic. You can invert the logical sense of the alarm relay output as well.

“C” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Terminal [11] active
state

C031

O/C-11

NO

Select logic conversion, two option
codes:
00

}normally open [NO]

01

}normally closed [NC]

U

00

00



Alarm relay active state

C036

O/C-RY

NC

Select logic conversion, two option
codes:
00

}normally open [NO]

01

}normally closed [NC]

U

01

01



3

54

Config

uri
ng Driv

e

Parameters

3

−54

&RQ¿JXULQJ'ULYH

Parameters