External Signal for DC Braking

When the terminal [DB] is turned ON, the
DC braking feature is enabled. Set the
following parameters when the external DC
braking terminal [DB] is to be used:

x A053 – DC braking delay time setting.

The range is 0.1 to 5.0 seconds.

x A054 – DC braking force setting. The

range is 0 to 100%.

The scenarios to the right help show how DC
braking works in various situations.

1. Scenario 1 – The [FW] or [RV] terminal is

ON. When [DB] is ON, DC braking is
applied. When [DB] is OFF again, the
output frequency ramps to the prior level.

2. Scenario 2 – The Run command is applied

from the operator keypad. When the [DB]
terminal is ON, DC braking is applied.
When the [DB] terminal is OFF again, the
inverter output remains OFF.

3. Scenario 3 – The Run command is applied

from the operator keypad. When the [DB]
terminal is ON, DC braking is applied
after the delay time set by A053 expires.
The motor is in a free-running (coasting)
condition. When the [DB] terminal is OFF
again, the inverter output remains OFF.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Applies DC injection braking during deceleration

07

DB

External DC
Braking

OFF

Does not apply DC injection braking during
deceleration

Valid for inputs:

C001~C005

Required settings

A053, A054

Notes:
x Do not use the [DB] input continuously or for a

long time when the DC braking force setting
A054 is high (depends on the motor application).

x Do not use the [DB] feature for continuous or

high duty cycle as a holding brake. The [DB]
input is designed to improve stopping
performance. Use a mechanical brake for
holding a stop position.

Example (requires input configuration—see

page 3–49

):

See I/O specs on

page 4–6.

5

4

3

2

1

L PCS P24

DB

[FW,RV]

1

0

[DB]

1

0

Output
frequency

Scenario 1

t

Run command
from operator

1

0

[DB]

1

0

Output
frequency

Scenario 2

t

Run command
from operator

1

0

[DB]

1

0

Output
frequency

Scenario 3

t

delay

A053

4

15

Operations and

Monitori

ng

4

−15

Operations and

Monitoring

Advertising