Alarm signal – XLT Hitachi X200 User Manual

Page 193

Advertising
background image

Alarm Signal

The inverter alarm signal is active when a fault has
occurred and it is in the Trip Mode (refer to the
diagram at right). When the fault is cleared the
alarm signal becomes inactive.

We must make a distinction between the alarm

signal

AL and the alarm relay

contacts

[AL0], [AL1]

and [AL2]. The signal AL is a logic function, which
you can assign to the open collector output terminal
[11] or the relay outputs.
The most common (and default) use of the relay is for AL, thus the labeling of its
terminals. Use an open collector output (terminal [11]) for a low-current logic signal
interface or to energize a small relay (50 mA maximum). Use the relay output to
interface to higher voltage and current devices (10 mA minimum).

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

when an alarm signal has occurred and has not
been cleared

05

AL

Alarm Signal

OFF

when no alarm has occurred since the last
clearing of alarm(s)

Valid for inputs:

11, AL0 – AL2

Required settings

C026, C036

Notes:

x By default, the relay is configured as normally

closed (C036=01). Refer to the next page for an
explanation.

x In the default relay configuration, an inverter

power loss turns ON the alarm output. the
alarm signal remains ON as long as the external
control circuit has power.

x When the relay output is set to normally closed,

a time delay of less than 2 seconds occurs after
powerup before the contact is closed.

x Terminal [11] is an open collector output, so the

electric specifications of [AL] are different from
the contact output terminals [AL0], [AL1],
[AL2].

x This signal output has the delay time (300 ms

nominal) from the fault alarm output.

x The relay contact specifications are in

“Control

Logic Signal Specifications” on page 4–6.

The

contact diagrams for different conditions are on
the next page.

Example for terminal [11] (default output
configuration shown – see

page 3-54

):

Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see

page 4-35 and 3-54

):

See I/O specs on

page 4-6

RY

Inverter output
terminal circuit

CM2

11

AL

AL1

Power
supply

Load

AL0

AL2

Inverter logic
circuit board

AL

Run

Stop

RUN

STOP
RESET

Trip

STOP
RESET

Fault

Fault

Alarm signal active

4

44

Operations and

Monitori

ng

4

−44

Operations and

Monitoring

Advertising