The following table lists parameters that configure the inverter’s serial communications
port. The settings affect how the inverter communication with a digital operator (such
as SRW-0EX), as well as a ModBus network (for networked inverter applications). The
settings cannot be edited via the network, in order to ensure network reliability. Refer to

“ModBus Network Communications” on page B-1

for more information on controlling

any monitoring your inverter from a network.

“C” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA)

Units

Selection of OPE / ModBus

C070

PARAM

REM

Two option codes:
02

}OPE or option

03

}ModBus (485)

U

02

02



Communication speed
selection

C071

COM BAU

4800

Three option codes:
04

}4800 bps

05

}9600 bps

06

}19200 bps

U

06

04

baud

Node allocation

C072

COM ADR

00001

Set the address of the inverter on
the network. Range is 1 to 32

U

1.

1.



Communication parity
selection

C074

COM PRTY

NON

Three option codes:
00

}No parity

01

}Even parity

02

}Odd parity

U

00

00



Communication stop bit
selection

C075

COM STP

1BIT

Range is 1 to 2

U

1

1

bit

Communication error select

C076

COM ESlct

None

Selects inverter response to
communications error.
Five options:
00

}Trip (Error code E60)

01

}Decelerate to a stop and trip

(Error code E60)

02

}Disable

03

}Free run stop (coasting)

04

}Decelerate to a stop

U

02

02



Communication error time-
out

C077

COM ETIM

000.00s

Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 sec

U

0.00

0.00

sec.

Communication wait time

C078

COM Wait

00000ms

Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms

U

0.

0.

msec.

3

60

Config

uri
ng Driv

e

Parameters

3

−60

&RQ¿JXULQJ'ULYH

Parameters