List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

A071

PID enable

R/W Enables PID function,

two option codes:
00

}PID Disable

01

}PID Enable

1068h

0, 1



A072

PID proportional gain

R/W Proportional gain has a range of

0.2 to 5.0

1069h

2 to 50

0.1

A073

PID integral time
constant

R/W Integral time constant has a

range of 0.0 to 150 seconds

106Ah

0 to 1500

0.1 sec

A074

PID derivative time
constant

R/W Derivative time constant has a

range of 0.0 to 100 seconds

106Bh

0 to 1000

0.1 sec

A075

PV scale conversion

R/W Process Variable (PV), scale

factor (multiplier), range of 0.01
to 99.99

106Ch

1 to 9999

0.01

A076

PV source setting

R/W Selects source of Process

Variable (PV), option codes:
00

}[OI] terminal (current in)

01

}[O] terminal (voltage in)

02

}ModBus network

10

}Calculate function output

106Dh

0, 1, 2, 3



A077

Reverse PID action

R/W Two option codes:

00

}PID input = SP-PV

01

}PID input = -(SP-PV)

106Eh

0, 1



A078

PID output limit

R/W Sets the limit of PID output as

percent of full scale,
range is 0.0 to 100.0%

106Fh

0 to 1000

0.1 %

A081

AVR function select

R/W Automatic (output) voltage

regulation, selects from three
type of AVR functions, three
option codes:
00

}AVR enabled

01

}AVR disabled

02

}AVR enabled except during

deceleration

1070h

0, 1, 2



A082

AVR voltage select

R/W 200V class inverter settings:

00

}200

01

}215

02

}220

03

}230

04

}240

400V class inverter settings:
00

}380

01

}400

02

}415

03

}440

04

}460

05

}480

1071h

0 to 5



A085

Operation mode
selection

R/W Two option codes:

00

}Normal operation

01

}Energy-saver operation

1072h

0, 1



A086

Energy saving mode
tuning

R/W Range is 0.0 to 100 %

1073h

0 to 1000

0.1 %